Warehouse Fire Sprinkler System Design Information
Below are examples of common warehouse sprinkler design scenarios and the general capacity of each system.
.20 GPM for 1,500 SQ. FT
Max Storage Height, Rack or Pile
Class I- IV Commodities: 12'
Flammable Liquids, Group A Plastics, Idle Pallets: 6'
.33 GPM for 3,000 SQ. FT
Max Storage Height, Rack or Pile
Class III Commodities: 20'
with minimum of 8' aisles, non encapsulated commodities, and conventional wood pallets
No-In rack sprinkling required
.45 GPM for 3,000 SQ. FT
Max Storage Height, Rack or Pile
Class IV Commodities: 20'
with minimum of 8' aisles, non encapsulated commodities, and conventional wood pallets
No-In rack sprinkling required
.60 GPM for 3,000 SQ. FT
Max Storage Height, Rack or Pile
Class III Commodities: 25'
with minimum of 8' aisles, non encapsulated commodities, and conventional wood pallets
No-In rack sprinkling required
Class IV Commodities: 22'
with minimum of 8' aisles, non encapsulated commodities, and conventional wood pallets
No-In rack sprinkling required
Early Suppression Fast Response (ESFR) Systems
ESFR systems are quick responding and high volume systems that provide exceptional protection for high piled storage occupancies. They are designed to suppress the fire by discharging a large volume of water directly to the fire to reduce the heat release rate and are ideal for maximizing the high pile storage potential of your warehouse.
This information is intended for reference only. Codes and technology are always changing, this is intended as a guide to give you the gist of how warehouse sprinkler system design and storage rack design are correlated.